1
1451 Belcher Road South, Largo, FL 33773 • USA
• Tel +1 (727) 447-6140 • Fax (727) 442-5699 •
[email protected]D-100 Dual Network Interface Installation Guide 07/14 - 1015 Page 21
Register
Address
Description Register Type Read/Write Comment
41009 Volume Rate – GPM Floating point register (1 of 2) Read Only
41010 Volume Rate – GPM Floating point register (2 of 2) Read Only
41011 Volume Rate – GPH Floating point register (1 of 2) Read Only
41012 Volume Rate – GPH Floating point register (2 of 2) Read Only
41013 Volume Rate – MGD Floating point register (1 of 2) Read Only
41014 Volume Rate – MGD Floating point register (2 of 2) Read Only
41015 Volume Rate – L/S Floating point register (1 of 2) Read Only
41016 Volume Rate – L/S Floating point register (2 of 2) Read Only
41017 Volume Rate – L/M Floating point register (1 of 2) Read Only
41018 Volume Rate – L/M Floating point register (2 of 2) Read Only
41019 Volume Rate – L/Hr Floating point register (1 of 2) Read Only
41020 Volume Rate – L/Hr Floating point register (2 of 2) Read Only
41021 Volume Rate – M³/Hr Floating point register (1 of 2) Read Only
41022 Volume Rate – M³/Hr Floating point register (2 of 2) Read Only
41071 Volume Rate – Ft³/S Floating point register (1 of 2) Read Only
41072 Volume Rate – Ft³/S Floating point register (2 of 2) Read Only
41073 Volume Rate – Ft³/M Floating point register (1 of 2) Read Only
41074 Volume Rate – Ft³/M Floating point register (2 of 2) Read Only
41023 Mass Rate – Lb/Hr Floating point register (1 of 2) Read Only
Mass units are only
available when using
F-2000 Vortex Meter.
41024 Mass Rate – Lb/Hr Floating point register (2 of 2) Read Only
41025 Mass Rate – Kg/Hr Floating point register (1 of 2) Read Only
41026 Mass Rate – Kg/Hr Floating point register (2 of 2) Read Only
41027 Supply Temperature – °F Floating point register (1 of 2) Read Only
41028 Supply Temperature – °F Floating point register (2 of 2) Read Only
41029 Return Temperature – °F Floating point register (1 of 2) Read Only
41030 Return Temperature – °F Floating point register (2 of 2) Read Only
41031 Supply Temperature – °C Floating point register (1 of 2) Read Only
41032 Supply Temperature – °C Floating point register (2 of 2) Read Only
41033 Return Temperature – °C Floating point register (1 of 2) Read Only
41034 Return Temperature – °C Floating point register (2 of 2) Read Only
41075 Generic Rate Ai3 Floating point register (1 of 2) Read Only
There are no engineering
units associated with
these registers.
41076 Generic Rate Ai3 Floating point register (2 of 2) Read Only
41077 Generic Rate Ai4 Floating point register (1 of 2) Read Only
41078 Generic Rate Ai4 Floating point register (2 of 2) Read Only
Register
Address
Description
Register
Range
Data
Range
Over
Range
Read/Write Comment
41001
Meter Operating Mode
Indicator
1 – 3
Not
applicable
Read Only
1 – indicates single mode
2 – indicates dual mode
3 – indicates bi-directional
mode
41002 Mode Status Indicator 1 – 2
Not
applicable
Read Only
1 - indicates heating mode
or forward direction
2 - indicates cooling mode
or reverse direction