GENERAL SPECIFICATIONS
ACCURACY
Analog Inputs: 0.1% of full scale
Analog Outputs: 0.1% of full scale
PROGRAMMING
Factory programmed for specic application.
MEMORY
Nonvolatile EEPROM memory retains all program
parameters and totalized values in the event of
power loss.
DISPLAY
Standard: 2-line Alphanumeric LCD displays ow
rate and ow total for the standard ow input
Alpha: 16 character, 0.2” high
Numeric: 7 digit, 0.4” high
Rate Display Range: 0 - 9,999,999
Totalizer Display Range: 0 - ,999,999
The totalizers will roll over to zero when maximum
count is exceeded.
OUTPUT SIGNALS
Pulse Outputs:
Two isolated contact closure outputs for separately
totalizing forward and reverse ow from the
standard ow input. Contact duration: 0.5, 1, 2
or 6 seconds (factory selectable). Default: 0.5
seconds
Maximum contact ratings: 100 mA, 50 VDC
Isolated contact closure output for indicating ow
direction
Maximum contact ratings: 100 mA, 50 VDC
Analog Outputs Options:
Single isolated analog output:
4-20 mA, 0-10 V or 0-5 V
Multiple (4) isolated analog outputs: 4-20 mA,
0-10 V or 0-5 V outputs
Network Interface Options
MODBUS RTU RS485
MODBUS RTU TCP/IP
BACnet MS/TP
BACnet UDP/IP
LONWORKS FTT10A
JCI Metasys - N2
Siemens Apogee - P1 FLN
INPUT SIGNALS
Standard: One totalizing ow input:
4-20 mA, contact closure or pulse
One contact closure input for ow
direction
Optional: Two auxiliary analog rate inputs:
4-20 mA
One digital totalizer input: pulse or
contact closure
Totalizer Range: 0-9,999,999 counts.
Total will rollover to zero when
maximum count is exceeded.
TEMPERATURE RANGE
Ambient temperature range: -20° F to 140° F
Do not install in direct sunlight.
MAINTENANCE
ONICON recommends periodic inspection and
recalibration for sensors connected to the D-100.
No other periodic maintenance is required for the
main unit.
MECHANICAL
Electronics Enclosure:
Standard: Steel NEMA 13, wall mount, 8”x10”x4”
Optional: NEMA 4
ELECTRICAL
This equipment is intended for INSTALLATION CATEGORY
(OVERVOLTAGE CATEGORY) II applications.
INPUT POWER:
Factory Selectable:
24 VAC: 20 - 28V, 50/60 Hz, 500 mA
120 VAC: 108 - 132V, 50/60 Hz, 250 mA
240 VAC: 207 - 253V, 50 Hz, 250 mA
INTERNAL FUSE RATING:
24 VAC - 1 Amp Slo-Blo, 3AG Fuse
120 VAC - 1/4 Amp Slo-Blo, 3AG Fuse
240 VAC - 1/8 Amp Slo-Blo, 3AG Fuse
OUTPUT:
24 VDC, 250 mA maximum
OVERCURRENT PROTECTIVE DEVICE RATINGS:
Supply mains overcurrent protective devices with the
following ratings:
120 VAC 50/60 Hz – 15 A
240 VAC 50 Hz – 6 A
WIRING:
Flow signals: Use 18-22 ga shielded cable – see ow
meter specication sheet or ow meter manual for
the correct number of conductors.
24 VAC input power: Use PVC jacketed copper cable
with a wire gauge suitable for the length of run and
required maximum current carrying capacity. The
installation must comply with all local, state and
federal building codes.
120/240 VAC input power: Use a three wire service with one
wire a protective earth ground. The installation must
comply with all local, state and federal building codes.
Note: Specications are subject to change without notice.
WARNING
All electrical connections must be made in
accordance with the imformation provided
here. Failure to do so will result in an
increases risk of injury.