SECTION 2.0: POINT FILE (.ddl)
The D-100 Display operates in one of two operating modes, unidirectional or bidirectional ow. The
tables below contain point information for each operating mode.
The .ddl le contains the information that identies the device to the N2 supervisory controller. It also
species the variables that are available to be transmitted to and from the device on the network.
The tables below contain the .ddl information.
2.1 UNIDIRECTIONAL FLOW POINT INFORMATION
Point Type
& Address
Engineering Units Point Description Range
AI2 Selectable (See volume/
mass rate table)
Volume or mass rate 0-999,999
AI3 User dened Generic analog input 0-999,999
AI4 User dened Generic analog input 0-999,999
ADF2 Selectable (See volume/
mass total table)
Volume or mass total 0-9,999,999
ADF5 User dened Auxiliary pulse input total (Di3) 0-9,999,999
BO2 None Reset total for ADF2 OVERRIDE Binary
Output, Object 2-ON
BO5 None Reset total for ADF5 OVERRIDE Binary
Output, Object 5-ON
2.2 BIDIRECTIONAL FLOW POINT INFORMATION
Point Type
& Address
Engineering Units Point Description Range
AI2 Selectable (See volume/
mass rate table)
Volume or mass rate 0-999,999
AI3 User dened Generic analog input 0-999,999
AI4 User dened Generic analog input 0-999,999
ADF2 Selectable (See volume/
mass rate table)
Mode 1 volume or mass total 0-9,999,999
ADF4 Selectable (See volume/
mass rate table)
Mode 2 volume or mass total 0-9,999,999
ADF5 User dened Auxiliary pulse input total (Di3) 0-9,999,999
BI1 None Flow Direction Indication 0-Forward
1-Reverse
BO2 None Reset total for ADF2 OVERRIDE Binary
Output, Object 2-ON
BO4 None Reset total for ADF4 OVERRIDE Binary
Output, Object 2-ON
BO5 None Reset total for ADF5 OVERRIDE Binary
Output, Object 5-ON