1.5 ADDITIONAL HARDWARE THAT MAY BE REQUIRED
1.5.1 Flow Conditioners
Flow conditioners may be required when an insufcient straight run of pipe is available
upstream of the proposed sensor location. ONICON provides ow conditioners as an
optional accessory.
ONICON ow conditioners are designed to be installed between two anges (provided
by installer) that are located a specic distance upstream of the ow sensor. The use of
ow conditioners signicantly reduces the upstream straight pipe length requirement
for ow sensor. See page 12 for straight run requirements. The size of the ow conditioner
must match the pipe size. Contact ONICON for Schedule 80 ow conditioners.
Part # Description
17381 1” Flow Conditioner, Sch40
17382 1¼” Flow Conditioner, Sch 40
17383 1½” Flow Conditioner, Sch40
17384 2” Flow Conditioner, Sch40
17385 2½” Flow Conditioner, Sch40
17386 3” Flow Conditioner, Sch40
17387 4” Flow Conditioner, Sch 40
17388 6” Flow Conditioner, Sch40
17389 8” Flow Conditioner, Sch40
1.5.2 Additional Remote Mount Cable
ONICON remote mount sensors are provided with 25 ft of cable. Additional cable lengths
of up to 1000 ft may be added without affecting the calibration of the sensor.
Part # Description
17350 25 ft of additional mount remote cable
17351 50 ft of additional remote mount cable
17352 100 ft of additional remote mount cable
Largest of the
two perforated
plates
Gaskets
FLOW
ANSI class flanges
(user supplied)
2 pipe
diameters
Flow conditioning
assembly is
inserted here
Flow sensor
inserts here