System-10 BTU Meter Manual 03/15 - 0651-16 / 18323 Page 14
MODULE
ELECTRONICS
SLEEVE
(Length varies with
thermowell length)
SPACER
END PIECE
PLASTIC
SENSOR
TEMPERATURE
SIGNAL (RED)
REFERENCE (BLACK)
SUPPLY
S/N 123456
ONICON TEMPERATURE SENSOR
TEMPERATURE SENSOR INSTALLED IN THERMOWELL
STANDARD THERMOWELL ASSEMBLY
FOR SYSTEM-10 BTU METER
SHOWN WITH TEMPERATURE SENSOR
0284
9-5-01
SIGNAL (RED)
REFERENCE
(BLACK)
SUPPLY
S/N 123456
5/8" MINIMUM
HOLE SIZE
1/2" HOLE FOR
CONDUIT OR
STRAIN RELIEF
FITTING.
NOTES: 1. If additional couplings are required, ensure that tip of thermowell remains in ow stream.
A-2
INCORPORA TED
1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699
www.onicon.com E-mail: [email protected]
PROVIDE 18-22 GA TWISTED
SHIELDED PAIR.
COIL ONE FOOT OF EXTRA
CABLE IN CONDUIT BOX.
1/2” NPT WELDED
BRANCH OUTLET
PLACE ELECTRONICS
MODULE IN BOX AFTER
CONNECTING WIRES.
RETAINING NUT
(Do not overtighten)
3.2.4 Flow Meter Installation
Determine which pipe (supply or return) has the longer unobstructed straight run. Install
the ow meter in the longest straight pipe run available. One temperature sensor can be
installed ve diameters downstream of the ow meter leaving enough clearance to remove
either sensor from the pipe without interference from the other sensor.
Also refer to the installation manual and/or other documentation that is provided with
your ONICON ow meter.
For F-1300 series inline turbine ow meters, refer to the documentation that is provided
with the ow meter.