1
1451 Belcher Road South, Largo, FL 33773 • USA
• Tel +1 (727) 447-6140 • Fax (727) 442-5699 •
[email protected]System-10-LON Network Interface Installation Guide 05/14 - 0654-5 / 16751 Page A-5
LONWORKS TWISTED PAIR NETWORK TERMINATION
52.3 Ohm
R1
100 uf electrolytic
C1
C2
100 uf electrolytic
100 uf electrolytic
C2
C1
100 uf electrolytic
R1
105 Ohm
+
+
Connect across Lon
bus at any point.
Connect across Lon network
at each end of the bus.
+
+
LonWorks Twisted Pair Network Termination
(Recommended Cable: Belden 85102 or equiv.)
Free Topology Network (Single Termination)
Bus Network (Dual Termination)