3.3.3 Isolated Analog Output (Optional):
The System-30 may be ordered from the factory with an optional analog output. This
output is factory congured to provide a linear output proportional to any one of the
following operating parameters: ow rate, energy rate, internal temperature sensor,
external temperature sensor or delta temperature. The format of this output may be
selected to provide a 4-20 mA, 0-10 Volt or 0-5 Volt signal.
This selection is eld congurable using the jumpers located on the analog output board
as shown below. Changing any of the displayed units or multipliers will affect the analog
output. If any unit or multiplier values are changed at the System-30 BTU Meter, the
analog output value will also be changed. If you are unsure of the ramications of any
changes you are contemplating, please contact ONICON for assistance.