5.3 BACnet
DEVICE OBJECT
Property Description and/or Example
Object _ Identier Instance number (1- 4,194,303)
Set via front panel user interface
Object _ Name Writeable (15 characters max) Default: ONICON
Object _ Type Device (8)
System _ Status OPERATIONAL (0)
Vendor _ Name ONICON Inc.
Vendor _ Identier 206
Model _ Name F-4000
Firmware _ Revision 2.04.06 (or later)
Application _ Software _ Version 012813-1338
Protocol _ Version 1
Protocol _ Revision 10
Protocol _ Services _ Supported Read property, read property multiple, write property
Protocol _ Object _ Types _ Supported Device, Analog Value, Binary Value
Object _ List Dx, AV0…AV28, BV0…BV10
Max _ APDU _ Length _ Supported 480
Segmentation _ Supported No _ Segmentation (3)
Local _ Time HH:MM:SS
Local _ Date MM:DD:YY
APDU _ Timeout 0
Number _ Of _ APDU _ Retries 0
Device _ Address _ Binding 0
Database _ Revision 2
ANALOG VALUE OBJECT List
BACnet Object Object _ Name BACnet Object Object _ Name
AV0 Flow AV15 Highest expected ow
AV1 Average ow AV16 Lowest expected ow
AV2 Raw ow AV17 Aeration alarm level
AV3 Volume total AV18 Slew mode selection
AV4 Sonic velocity AV19 Time averaging period
AV5 Delta time AV20 Smart slew seed
AV6 Valc AV21 Device status
AV7 Aeration AV22 Site name
AV8 Deadband control AV23 Version information
AV9 Batch/sample total AV24 Date/time last reset
AV10 High ow alarm level AV25 Op sys P/N
AV11 Low ow alarm level AV26 Firmware checksum
AV12 Vs alarm level AV27 Compile time info
AV13 Flow velocity AV28 System date/time
AV14 Signal