[email protected]F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838 Page 40
ANALOG VALUE OBJECT Properties
Property Identier Description and/or Example R/W
Object_Identier Unique identier number R
Object_Type 2 – Analog Value R
Present_Value Real (Floating point) Number R
Description Character string representing engineering units (e.g. GAL/MIN) R
Units No-units (95) R
Status_Flags IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE (e.g. 0,0,0,0) R
Event_State 0 - NORMAL R
Out_Of_Service 0 - FALSE R
BINARY VALUE OBJECTS
BACnet Object Description
BV0 Totalizer reset (Read/Write)
BV1 Spacing alarm (Read only)
BV2 Empty alarm (Read only)
BV3 Rate alarm(Read only)
BV4 Fault alarm (Read only)
BV5 Aeration alarm (Read only)
BV6 Memory alarm (Read only)
BV7 Makeup alarm (Read only)
BV8 Interface alarm (Read only)
BV9 Pig alarm (Read only)
BV10 Zeromatic alarm (Read only)
BINARY VALUE OBJECT Properties
Property Identier Description and/or Example R/W
Object_Identier Unique identier number R
Object_Type 5 – Binary Value R
Present_Value Binary (e.g. 0 or 1) R/W*
Description Character string representing object function (e.g. Aeration Alarm) R
Priority_Array Manual Operator (8) R
Status_Flags IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE (e.g. 0,0,0,0) R
Event_State NORMAL R
Out_Of_Service FALSE R