Onicon F-4000 Series Manual de usuario Pagina 41

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 52
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 40
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
F-4000 Series Ultrasonic Flow Meter Manual 05/15 - 0707-13 / 18838 Page 41
BACnet Protocol Implementation Conformance Statement
Date: April 13, 2012
Vendor Name: ONICON, Inc.
Product Name: F-4000 Series Ultrasonic Flow Meter
Product Model Number: F-4000
Application Software Version: 012813-1338
Firmware Revision: 2.04.06
BACnet Protocol Revision: 1
Product Description: Clamp-on ultrasonic ow meter for liquids
BACnet Standardized Device Prole (Annex L):
o BACnet Operator Workstation (B-OWS)
o BACnet Advanced Operator Workstation (BAWS)
o BACnet Operator Display (B-OD)
o BACnet Building Controller (B-BC)
o BACnet Advanced Application Controller (BAAC)
o BACnet Application Specic Controller (BASC)
þ BACnet Smart Sensor (B-SS)
o BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building blocks Supported (Annex K):
þ K.1.2 BIBB – Data Sharing – ReadProperty-B (DS-RP-B)
þ K.1.4 BIBB – Data Sharing – ReadPropertyMultiple-B (DS-RPM-B)
þ K.1.8 BIBB – Data Sharing – WriteProperty-B (DS-WP-B)
Segmentation Capability:
Segmentation is not supported
Standard Object Types Supported:
þ Device Object
þ Binary Value Object
þ Analog Value Object
Dynamically Creatable Object: None
Dynamically Deletable Object: None
Optional Properties Supported:
Device Object:
PROP_LOCAL_TIME
PROP_LOCAL_DATE
PROP_DESCRIPTION
Binary Value Object:
PROP_DESCRIPTION
Analog Value Object:
PROP_DESCRIPTION
Operational Writable Properties: None
Operational Conditional Writable Properties: None
Proprietary Properties: None
Range Restrictions: None
Data Link Layer Options:
o BACnet IP, (Annex J)
o BACnet IP, (Annex J), Foreign Device
o ISO 8802-3, Ethernet (Clause 7)
o ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
o ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s)
o MS/TP master (Clause 9), baud rate(s):
þ MS/TP slave (Clause 9), baud rate(s): 300, 1200, 2400, 4800, 9600, 38400
o Point-To-Point, EIA 232 (Clause 10), baud rate(s):
Vista de pagina 40