3.3.2 Electrical Wiring
Connect all Btu meter signal outputs to terminal strip TB1 and/or TB4 (optional
communication output) as shown below. Then connect the 24 V AC/DC input power to
terminal strip TB1. The standard SYSTEM-30 is congured for 24 V AC 50/60 Hz
operation or 24 V DC operation. Do not connect the 24 V AC/DC source until all other
signal connections have been made and veried.
CAUTION
Only qualied service personnel should make connections between the System-30-MOD BTU
Meter and the user’s external equipment. ONICON assumes no responsibility for damaged caused
tot he external equipment as a result of an improper installation.