Register
Address
Description
Register
Range
Data
Range
Over
Range
Read/Write Comment
41001
Meter Operating Mode
Indicator
1 – 3
Not
applicable
Read Only
1 – indicates single mode
2 – indicates dual mode
3 – indicates bi-directional
mode
41002 Mode Status Indicator 1 – 2
Not
applicable
Read Only
1 - indicates heating mode
or forward direction
2 - indicates cooling mode
or reverse direction
Register
Address
Description Register Type Read/Write Comment
41003 Energy Rate – Btu/Hr Floating point register (1 of 2) Read Only
41004 Energy Rate – Btu/Hr Floating point register (2 of 2) Read Only
41005 Energy Rate – kW Floating point register (1 of 2) Read Only
41006 Energy Rate – kW Floating point register (2 of 2) Read Only
41007 Energy Rate – Tons Floating point register (1 of 2) Read Only
41008 Energy Rate – Tons Floating point register (2 of 2) Read Only
41009 Volume Rate – GPM Floating point register (1 of 2) Read Only
41010 Volume Rate – GPM Floating point register (2 of 2) Read Only
41011 Volume Rate – GPH Floating point register (1 of 2) Read Only
41012 Volume Rate – GPH Floating point register (2 of 2) Read Only
41013 Volume Rate – MGD Floating point register (1 of 2) Read Only
41014 Volume Rate – MGD Floating point register (2 of 2) Read Only
41015 Volume Rate – L/S Floating point register (1 of 2) Read Only
41016 Volume Rate – L/S Floating point register (2 of 2) Read Only
41017 Volume Rate – L/M Floating point register (1 of 2) Read Only
41018 Volume Rate – L/M Floating point register (2 of 2) Read Only
41019 Volume Rate – L/Hr Floating point register (1 of 2) Read Only
41020 Volume Rate – L/Hr Floating point register (2 of 2) Read Only
41021 Volume Rate – M³/Hr Floating point register (1 of 2) Read Only
41022 Volume Rate – M³/Hr Floating point register (2 of 2) Read Only
41023 Mass Rate – Lb/Hr Floating point register (1 of 2) Read Only
Mass units are only
available when using
F-2000 Vortex meter
41024 Mass Rate – Lb/Hr Floating point register (2 of 2) Read Only
41025 Mass Rate – Kg/Hr Floating point register (1 of 2) Read Only
41026 Mass Rate – Kg/Hr Floating point register (2 of 2) Read Only
41027 Supply Temperature – °F Floating point register (1 of 2) Read Only
41028 Supply Temperature – °F Floating point register (2 of 2) Read Only
41029 Return Temperature – °F Floating point register (1 of 2) Read Only
41030 Return Temperature – °F Floating point register (2 of 2) Read Only
41031 Supply Temperature – °C Floating point register (1 of 2) Read Only
41032 Supply Temperature – °C Floating point register (2 of 2) Read Only
41033 Return Temperature – °C Floating point register (1 of 2) Read Only
41034 Return Temperature – °C Floating point register (2 of 2) Read Only