5.3 TROUBLESHOOTING GUIDE FOR SYSTEM-10-P1 BTU MEASUREMENT SYSTEM
NOTE: Also refer to the COMMISSIONING GUIDE located on the preceding pages.
REPORTED PROBLEM POSSIBLE SOLUTIONS
For turbine meters -
No ow signal/ energy rate
(while hydronic system is
active)
Verify 24 VDC supply voltage to the ow meter.
For insertion meters, verify the ow meter is correctly inserted into
the pipe (using depth gage).
For insertion meters, verify that the ow meter electronics enclosure
is parallel with the pipe.
Verify correct wiring to the ow meter (see wiring diagram).
For turbine meters, check turbine(s) for clogging due to debris.
If none of the above, check hydronic system to ensure that ow is
really present in the line.
NOTE: Flow meter function cannot be veried by blowing on the
turbine(s). The sensing system requires a conductive liquid to
operate. You can test it by swirling it around in a bucket of water
and looking for the ow indicator LED to ash at the System-10.
Displayed ow rate too high
or too low
Verify pipe size. Contact ONICON if pipe size is different from
calibration tag.
For insertion meters, verify that meter is inserted correctly into the
pipe (using depth gage).
For insertion meters, verify that the ow meter electronics enclosure
is parallel with the pipe.
For dual turbine meters, conrm that both turbines produce pulses.
For turbine meters, check turbine(s) for debris.
Verify supply voltages (to BTU meter and ow meter).
Displayed temperature(s) too
high or too low vs. expected
values
Verify wiring to temperature sensor(s), including polarity.
Verify that thermowells are inserted into the ow stream and
that the temperature sensors are completely inserted into the
thermowells.
Data not available at the
control system
(Device ofine)
Verify that the device address has been correctly programmed into
the System-10-P1.
Verify that the System-10-P1 has been properly characterized in the
eld panel.
Press and hold switch S-1 for two seconds.
Control system displays
incorrect multipliers and/or
units vs. displayed
values
Verify that the units and multipliers shown on the System-10-P1
display agree with the values shown on the Floor Level Network.
The device must be re-characterized in the eld panel whenever the
System-10-P1 units or multipliers are changed.
For technical assistance, contact ONICON at (727) 447-6140.