1.4 ADDITIONAL REQUIRED HARDWARE
ONICON offers a wide variety of ow meters to satisfy most hydronic energy metering applications.
Model F-1100 Single Turbine Insertion Flow Meter
For line sizes 1¼” and larger with 25 diameters of straight pipe run available for
installation. (F-1100 can also be used with 1” copper lines.)
Model F-1200 Dual Turbine Insertion Flow Meter
For line sizes 2½” and larger with 15 diameters of straight pipe run available for
installation.
Model FB-1200 Bi-Directional Insertion Flow Meter
For bi-directional ow applications in line sizes 2½” and larger with 20 diameters of
straight pipe run available for installation.
Model F-1300 Inline Turbine Flow Meter
For line sizes ¾” and 1” with 25” of straight pipe run available for installation.
Model F-3500 Insertion Electromagnetic Flow Meter
For line sizes 3” and larger. (See F-3500 manual for straight run requirements).
Model F-26** Inline Vortex Flow Meter
(Suitable for use in higher temperature applications).
For line sizes 1” through 12” (See Vortex Flow Meter manual for straight run requirements).
Model F-31** / F-32** Inline Electromagnetic Flow Meter
For line sizes ¼” and larger with 5 diameters of straight pipe run available for installation.
Please refer to ONICON’s ow meter literature, or contact ONICON for help in selecting
the ow meter that will best t your requirements.
1.5 WORKING ENVIRONMENT
The SYSTEM-10 was designed for installation and use in typical industrial environments that are
free of corrosive liquids and fumes, direct liquid exposure, temperature extremes and vibrations.
Do not expose the meter to direct sunlight.
The operating ambient air temperature range is -20° F to 140° F. The electrical power should be
relatively clean, free of high frequency noise, large voltage transients, and protected from power
surges and brown outs.
1.6 WARRANTY & SERIAL NUMBER
Warranty
ONICON’s 2-year “No-fault” warranty reduces start-up costs by extending coverage for
incidental damage during installation. Certain exclusions apply. Please refer to ONICON’s
Conditions of Sale for details.
Serial Number
The serial number of your SYSTEM-10 is located outside and inside the main unit. All
components of your SYSTEM-10 (ow meter, temperature sensors, and main unit) should bear
identical serial numbers if ordered together. The serial numbers are unique identiers that you
should have available when contacting ONICON for assistance regarding your system.