System-40-BAC BTU Meter Manual 03/15 - 1045-2 Page 23
6.4 ANALOG INPUT(S)
Property Default Value Read-only or
Writable
Comment
Object Identier Analog-input,1 to analog-input,10 Read-only
Object Name Various Read-only
Object Type Analog-input Read-only
Present Value REAL Writable
Description Analog-input,# Name Read-only
Status Flags (F,F,F,F) Read-only
Event State normal Read-only
Reliability No-fault-detected Read-only
Out-of-Service FALSE Writable
Update interval 100 Read-only
Units
Various
Read-only
Min-Present-Value -1000000000 Read-only
Max-Present-Value 1000000000 Read-only
Resolution 0.000001 Read-only
6.5 ANALOG VALUE(S)
Property Default Value Read-only or
Writable
Comment
Object Identier Analog-value,1 to analog-value,22 Read-only
Object Name Various Read-only
Object Type Analog-value Read-only
Present Value REAL Writable
Description Analog-value,# Name Read-only
Status Flags (F,F,F,F) Read-only
Event State normal Read-only
Reliability No-fault-detected Read-only
Out-of-Service FALSE Writable
Units Various Read-only
Priority Array
{NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL}
Read-only
Relinquish Default 0 Read-only