11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
System-40-BAC BTU Meter Manual 03/15 - 1045-2 Page 24
6.6 BINARY VALUE(S)
Property Default Value Read-only or
Writable
Comment
Object Identier Binary-value,1 to binary-value,10 Read-only
Object Name Various Read-only
Object Type Binary-value Read-only
Present Value 0 Writable
Description Binary-value,# Name Read-only
Status Flags (F,F,F,F) Read-only
Event State normal Read-only
Reliability No-fault-detected Read-only
Out-of-Service FALSE Writable
Elapsed Active Time Various Read-only
Priority Array
(NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL)
Read-only
Relinquish Default 0 Read-only
6.7 MULTI STATE VALUE
Property Default Value Read-only or
Writable
Comment
Object Identier Multi-state-value,1 Read-only
Object Name Meter Status Read-only
Object Type multi-state-value Read-only
Present Value 1 Writable
Description Multi-state-value,# Name Read-only
Status Flags (F,F,F,F) Read-only
Event State normal Read-only
Reliability No-fault-detected Read-only
Out-of-Service FALSE Writable
Number of States 11 Read-only
State Text
Normal, Low Supply Temperature,
High Supply Temperature, Low
Return Temperature, Delta T<
Minimum, High Energy Rate, Low
Signal Quality, Comm Error, Low
Supply Voltage, System Fault
Read-only
Relinquish Default 0 Read-only