6.8 TREND LOG MULTIPLE
Property Default Value Read-only or
Writable
Comment
Object Identier Trend-log-multiple,1 Read-only
Object Name Log Data Read-only
Object Type Trend-log-multiple Read-only
Description Trend-log-multiple,# Name Read-only
Status Flags (F,F,F,F) Read-only
Event State normal Read-only
Reliability No-fault-detected Read-only
Enable TRUE Writable
Log Device Property Read-only See Note Below
Logging Type POLLED Read-only
Log Interval
9000
Writable
Stop When Full FALSE Read-only
Buffer Size 480 Read-only
Log Buffer Read-only
Record Count 0 Writable
Total Record Count 0 Read-only
Note: Log Device Property – Log intervals can be set over a range of 30 seconds to 60
minutes. The following objects can be logged:
Analog-input, 1 Energy Rate
Analog-input, 2 Volume Rate
Analog-input, 3 Supply Temperature
Analog-input, 4 Return Temperature
Analog-input, 5 Delta Temperature
Analog-value, 1 Volume Total Mode 1
Analog-input, 2 Volume Total Mode 2
Analog-value, 9 Volume Total Mode 1
Analog-input, 10 Volume Total Mode 2
Multi-state-value, 1 Meter Status