11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204 Page 18
1.3.2 Line Size / Process Connections / Materials
The in-line model is built for line sizes ½" through 4" wafer or ½" through 8" anged
design using ANSI 150, 300, 600, PN16, 40, or 64 class anges.
The insertion model can be used in line sizes 2" and greater and is built with a packing
gland design using 2" NPT, or 2" anged connections (ANSI 150, 300, 600, PN16, 40, or 64
class anges). The packing gland design can be ordered with a permanent or removable
retractor.
The standard in-line model is built with 316L stainless steel, A105 carbon steel and
Hastelloy C-276 versions are available via special order. The insertion model is built with
316L stainless steel.
1.3.3 Flow Meter Electronics
The ow meter electronics are available mounted directly to the ow body, or mounted
remotely. The electronics housing may be used indoors or outdoors, including wet
environments. Available input power options are: DC loop powered (2-wire), DC powered,
or AC powered. Three analog output signals are available for your choice of three of the
ve process variables: mass ow rate, volumetric ow rate, temperature, pressure or uid
density. A pulse output signal for remote totalization and BACnet, MODBUS or HART
communications is also available.
Each meter includes a local 2 x 16 character LCD display housed within the enclosure.
Local operation and reconguration is accomplished using six pushbuttons operated via
nger touch. For hazardous locations, the six buttons can be operated with the electronics
enclosure sealed using a hand-held magnet, thereby not compromising the integrity of the
hazardous location certication.
The electronics include nonvolatile memory that stores all conguration information. The
nonvolatile memory allows the ow meter to function immediately upon power up or after
an interruption in power. All owmeters are calibrated and congured for the customer’s
ow application.