4.3.3.3. Binary Input Object:
Vortex Mass Flow Meters Binary Input type objects are described
in the below Table.
Object Instance Object Name Description
1 Alarm1 The status of the three alarms may be monitored via the Modbus
command. The value returned indicates the state of the alarm, and will be
1 only if the alarm is enabled and active. A zero value is transmitted for
alarms that are either disabled or inactive
2 Alarm2
3 Alarm3
4 External TBD
Note - Binary Input 4, Present value always read zero, because no information available from
client, so the polarity property doesn’t impact on Present value property when the Out of
service property is false.
3.4. Binary Value Object:
Vortex Mass Flow Meters Binary Value type objects are described
in the below Table.
Object Instance Object Name Description
1 Reset Reset's Totalizer
4.3.4. ANNEX - BACnet PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT
Date: 19-April-2012
Vendor Name: ONICON Incorporated
Product Name: F-2000 Series Vortex Meter
Product Model Number: F-2600 / F-2700
Applications Software Version: 1.07
Firmware Revision: N/A
BACnet Protocol Revision: 4
Product Description: Multivariable Vortex Flow Meter
BACnet Standardized Device Prole (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
√ BACnet Application Specic Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)