Properties of Analog Input/Value Objects Type
ID Name
Present
Value
Status
Flags
Event
State
Out of
Service
Units
AI1 Volume Flow ? F,F,F,F Normal False ?
AI2 Mass Flow ? F,F,F,F Normal False ?
AI3 Temperature 1 ? F,F,F,F Normal False ?
AI4 Temperature 2 ? F,F,F,F Normal False ?
AI5 Pressure ? F,F,F,F Normal False ?
AI6 Density ? F,F,F,F Normal False ?
AI7 Energy Flow ? F,F,F,F Normal False ?
AI8 Totalizer 1 ? F,F,F,F Normal False ?
AI9 Totalizer 2 ? F,F,F,F Normal False ?
AI10 StatusRegister ? F,F,F,F Normal False ?
AI11 Channel 1 (4-20mA) ? F,F,F,F Normal False ?
AI12 Channel 2 (4-20mA) ? F,F,F,F Normal False ?
AI13 Channel 3 (4-20mA) ? F,F,F,F Normal False ?
AI14 Scaled Freq ? F,F,F,F Normal False ?
AI15 Flow Velocity ? F,F,F,F Normal False ?
AI16 Viscosity ? F,F,F,F Normal False ?
AI17 Frequency ? F,F,F,F Normal False ?
AI18 VorTex Amp ? F,F,F,F Normal False ?
AI19 FilterSetting ? F,F,F,F Normal False ?
Properties of Analog Input/Value Objects Type
ID Name
Present
Value
Status
Flags
Event
State
Out of
Service
Polarity
BI1 Alarm1 ? F,F,F,F Normal False ?
BI2 Alarm2 ? F,F,F,F Normal False ?
BI3 Alarm3 ? F,F,F,F Normal False ?
BI4 External ? F,F,F,F Normal False ?
Properties of Analog Input/Value Objects Type
ID Name
Present
Value
Status
Flags
Event
State
Out of
Service
out-of-
service
BV1 Reset ? F,F,F,F Normal False False
Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s)
√ MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400
MS/TP slave (Clause 9), baud rate(s):
Point-To-Point, EIA 232 (Clause 10), baud rate(s):
Point-To-Point, modem, (Clause 10), baud rate(s):
LonTalk, (Clause 11), medium:
Other: