F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204 Page 61
3.3.4 Alarms Menu
Password
ENTER
Use
keys to access menus
Alarms
Menu
Relay Alarm 1
More >
ENTER
Run Mode
Relay Alarm 2
More >
Relay Alarm 3
More >
Alarm LOG
xx Files (ENTER)
Clear Alarm LOG?
YES or NO
<Measure> units
xxxx
xxxx
xxxx
Alarm File
Time
Date
(Press EXIT to return
to Alarm LOG.)
* see below
Physical Layer does not exist on Two Wire
Mass - Accessible via HART
<Measure>
None
Mass
Volume
Temp 1,2
Press
Density
**
Energy
<Measure>
None
Mass
Volume
Temp 1,2
Press
Density
**
Energy
<Measure>
None
Mass
Volume
Temp 1,2
Press
Density
**
Energy
<Mode>
None
HIGH Alarm (>)
LOW Alarm (<)
<Mode>
None
HIGH Alarm (>)
LOW Alarm (<)
<Mode>
None
HIGH Alarm (>)
LOW Alarm (<)
<Measure> units
<Measure> units
*
**
Energy Meters Only
Example for Setting an Alarm
The following shows how to set Relay Alarm 1 to activate if the mass ow rate is greater
than 100 lb/hr. You can check the alarm conguration in the Run Mode by pressing the
keys until Alarm (1) appears. The lower line displays the mass ow rate at which the
alarm activates. Note: All outputs are disabled while using the Set-up Menus.
First, set the desired units of measurement:
1. Use keys to move to the Units Menu (see to page 64).
2. Press key until Mass Flow Unit appears. Press ENTER.
3. Press key until lb appears in the numerator. Press key to move the underline
cursor to the denominator. Press the key until hr appears in the denominator. Press
ENTER to select.
4. Press key until Units Menu appears.
Second, set the alarm:
1. Use keys to move to the Alarms Menu.
2. Press the key until Relay Alarm 1 appears.
3. Press key to access Measure selections. Press ENTER and use the key to select
Mass. Press ENTER.
4. Press key to select the alarm Mode. Press ENTER and use key to select HIGH
Alarm. Press ENTER.
5. Press key to select the value that must be exceeded before the alarm activates.
Press ENTER and use keys to set 100 or 100.0. Press ENTER.
6. Press the EXIT key to save your changes. (Alarm changes are always permanently
saved. Up to three relay alarm outputs are available depending on meter
conguration.)